Wire cross-sections
16 May 2020 - tsp
Last update 09 Dec 2020
5 mins
Since Iโm not always having the technical regulations at hand when Iโm doing
some cabling Iโve summarized the required cross sections for various cabling
methods and their associated maximum current carrying capacity.
Disclaimer: There is no guarantee that the values presented on this page
are correct in your regulatory domain or at the time of reading - if you do
anything with electrical installations refer to your official regulations - and
beware which installations are allowed to be done by non-professionals and which have
to be done by professionals). This table is noted here just as a quick reference
for myself.
Note that all data is related to regulations in Austria.
Maximum voltage drop
The voltage drop due to cable loss is limit to at most 4 percent. One has to note
that 1 percent is reserved for voltatge drop between attachment point and measurement
equipment of the supplier.
Main supply cables (400/230V)
Residental areas have to be connected to the electricity grid with at least the
following wire crosssections inside the specified pipe diameters with the
given maximum length. The dimensions have been determined to match a maximum
power of $18 kW$ per unit and a maximum voltage drop of $1%$ between the
attachment point to the grid and measurement equipment.
Number of flats | Cross section copper ($mm^2$) | Minimum pipe size ($mm$) | Maximum length ($m$) |
1-3 | 16 | 50 | 30 |
4-6 | 25 | 50 | 40 |
7-10 | 35 | 63 | 40 |
In case of a larger number of units, higher desired wattage of the consumers
or longer cable lengths calculations have to be done specifically for the
given situation. Normally one uses multiple main supply cables when attaching
more than 11 units since handling of cables with smaller or up to ยง35 mm^2$
cross section is way simpler than larger diameter wires.
All cables between the main attachment point and measurement equipment has
to be done in pipes (enclosed in a way that access to steal electricity is
prevented) or burried in the ground - without any interruptions or splices.
They should be generally accessible (without entering a specific flat)
Maximum current ($A$) for given Wire diameters of PVC isolated cables

Assumptions:
- PVC isolated cables
- Maximum temperature of 70 degree celsius
- Environment temperature 25 degree celsius
- Only a single batch of wires is used
In case any of these assumptions are not met there are correction factors noted inside the
technical regulations.
Cross-section ($mm^2$) | Inside insulated walls | Inside or on top of uninsulated walls | Multi-core wire on walls or below plaster | Household/Handheld devices | Inside earth |
Single-core, inside pipes | Multi-core, with or without pipe | Single-core, inside pipes | Multi-core, with pipe |
2 wires | 3 wires | 2 wires | 3 wires | 2 wires | 3 wires | 2 wires | 3 wires | 2 wires | 3 wires |
1.5 | 13 | 13 | 13 | 13 | 16 | 16 | 16 | 16 | 16 | 16 | 16 | 25 |
2.5 | 20 | 16 | 16 | 16 | 25 | 20 | 20 | 20 | 25 | 25 | 20 | 25 |
4 | 25 | 25 | 25 | 20 | 25 | 25 | 25 | 25 | 35 | 35 | 25 | 40 |
6 | | 25 | | 25 | | 35 | | 35 | | 40 | | 50 |
10 | | 40 | | 35 | | 50 | | 50 | | 63 | | 63 |
16 | | 50 | | 50 | | 63 | | 63 | | 80 | | 80 |
25 | | 63 | | 63 | | 80 | | 80 | | 100 | | 100 |
35 | | 80 | | 80 | | 100 | | 100 | | 125 | | 125 |
Pipe sizes
Regulations define the minimum nominal diameter of pipes used for given wire
cross-sections:
Cross-section ($mm^2$) | Wires |
1 | 2 | 3 | 4 | 5 |
1.5 | 16 | 16 | 16 | 16 | 20 |
2.5 | 16 | 16 | 16 | 20 | 20 |
4 | 16 | 16 | 16 | 25 | 32 |
6 | 16 | 20 | 25 | 32 | 40 |
10 | 20 | 25 | 25 | 40 | 40 |
16 | 25 | 32 | 40 | 40 | 50 |
25 | 25 | 40 | 40 | 50 | 50 |
35 | 32 | 40 | 50 | 50 | 63 |
50 | 32 | 50 | 50 | 63 | 63 |
70 | 40 | 50 | 63 | 63 | 63 |
95 | 40 | 50 | 63 | 63 | |
120 | 50 | 63 | 63 | 63 | |